Project · Municipality of Kütahya · Inner Aegean · 2024–2025

Network in the “critical” band: 432 faults over 348.5 km.

In an acoustic leak detection service carried out with the Water and Sewerage Directorate, the fault density found after listening to the 300 km of the initial tender rose well above international thresholds; the scope was extended and the findings were confirmed.

Initial scope · main listened
300km
Initial scope · leaks/faults found
403count
Tender extension · additional listening
48.5km
Tender extension · additional faults
29count
Total main listened
348.5km
Total faults found
432count
Fault density
1.34faults/km/yr

Comparison with international thresholds

Acoustic detection performance is usually assessed by the number of faults per km per year. The 1.34 faults/km/yr found in the initial work at Kütahya is:

  • about 3 times the acceptance limit of EU Directive 2020/2184 (~0.50),
  • about ten times the AWWA North American average (~0.09),
  • within the 1.0–4.0 band defined in academic work as “requiring rehabilitation”.

The extension decision and its confirmation

The high density showed the faults to be systematic, not random. Finding 29 more faults in the 48.5 km of additional listening carried out under Public Procurement Law No. 4734 confirmed the initial assessment.

Why early detection matters

Acoustic detection catches the great majority of faults before the ground breaks; it reduces the risk of a sudden burst, the cost of an emergency crew and the expense of surface repair.

Acoustic correlation · locating between two contact points Acoustic correlation · locating between two contact points
Network main survey Network main survey

Source: the justification report for the Acoustic Leak Detection Service and the field record tables. Comparison values are based on peer-reviewed publications and institutional documents (AWWA 2018; EU Directive 2020/2184; MDPI Water 2023).

Result

Systematic surveying is essential.

The findings showed that the network as a whole is in a serious deterioration process and that a regular, planned acoustic survey programme is needed. Every fault found was passed to the municipality with an urgent-repair priority.